NOBEL FC2 – With 2 heat exchangers
MODEL | 160 | 200 | 300 | 400 | 500 | 800 | 1000 | 1500 | 2000 | |
---|---|---|---|---|---|---|---|---|---|---|
TOTAL CAPACITY (EN 12897) | lt | 153 | 187 | 283 | 378 | 443 | 763 | 952 | 1500 | 2000 |
NET WEIGHT | kg | 72 | 88 | 121 | 143 | 166 | 248 | 289 | 417 | 640 |
INSULATION | mm | 50 | 50 | 50 | 50 | 50 | 70 | 70 | 80 | 80 |
HEAT EXCHANGER SURFACE (S1 – LOWER HE) | m² | 0.64 | 0.85 | 1.27 | 1.65 | 2.06 | 2.45 | 3.18 | 3.86 | 4.65 |
HEAT EXCHANGER SURFACE (S2 – UPPER HE) | m² | 0.42 | 0.62 | 0.85 | 0.97 | 0.96 | 1.46 | 1.49 | 1.86 | 2.26 |
HEAT EXCHANGER CAPACITY (S1) | lt | 3.83 | 5.10 | 7.66 | 10.21 | 12.44 | 20.11 | 26.00 | 31.27 | 37.67 |
HEAT EXCHANGER CAPACITY (S2) | lt | 2.55 | 3.83 | 5.10 | 5.87 | 6.06 | 11.96 | 12.17 | 15.07 | 18.31 |
HEAT EXCHANGER OUTPUT (60-80°C) (S1) | kW | 17 | 26 | 34 | 45 | 52 | 57 | 78 | 63 | 72 |
HEAT EXCHANGER OUTPUT (60-80°C) (S2) | kW | 13 | 16 | 26 | 25 | 31 | 39 | 33 | 30 | 35 |
HEAT EXCHANGER CONTINUOUS FLOW RATE (60-80°C) (S1) | L/h | 418 | 639 | 835 | 1106 | 1278 | 1401 | 1917 | 1548 | 1769 |
HEAT EXCHANGER CONTINUOUS FLOW RATE (60-80°C) (S2) | L/h | 319 | 393 | 639 | 614 | 762 | 958 | 811 | 737 | 860 |
ΗΕΑΤ LOSSES ΔΤ 45K | kWh/24h | 1.4 | 1.5 | 1.7 | 2.2 | 2.5 | 3.2 | 3.5 | 4.24 | 6.5 |
ENERGY EFFICIENCY CLASS | B | B | B | C | C | C | C | C | C | |
Heat Exchanger Pressure drop C1 | mbar | 18 | 18 | 27 | 28 | 60 | 53 | 117 | – | – |
Heat Exchanger Pressure drop C2 | mbar | 3 | 9 | 19 | 26 | 26 | 12 | 12 | – | – |
MAXIMUM OPERATIONAL TEMPERATURE | °C | 95 | 95 | 95 | 95 | 95 | 95 | 95 | 95 | 95 |
RATED PRESSURE | bar | 10 | 10 | 10 | 10 | 10 | 8 | 8 | 8 | 8 |
RATED PRESSURE OF THE HEAT EXCHANGER | bar | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 |
NL FACTOR (S1) | 2.8 | 4.0 | 8.2 | 12.5 | 19 | 26 | 35 | 56 | 82 | |
NL FACTOR (S2) | 0.5 | 0.8 | 2.5 | 2.3 | 3.2 | 10 | 16 | 17 | 26 |