Thermostatic 20°-50°C head with remote sensor.
Three-way mixing valve
By-pass valve with manual adjustment
Element holder probe
G1” pipe unions with O-ring seal for the collector
Fixed point temperature regulating group. Max.pressure valve and flowmeter. Thermostatic head 20-50°C with remote sensor and cockpit with 1/2” connection.
Function
The fixed point regulation unit performs the function of keeping the
flow temperature constant, at the set value, to the underfloor heating
system with low-temperature circuit.
The temperature is adjusted by means of a three-way thermostatic
valve equipped with a thermostat control device with a remote sensor
The thermostatic control with a remote sensor that is to be installed on the 3-way mixing valve is supplied with the
“fixed point regulating unit”. By adjusting the thermostatic control it is
possible to set the temperature of the heat transfer fluid that circulates
within the low-temperature circuit of the radiant panels.
The thermostatic control has an adjustment range that goes from 20
to 50 °C, it is advisable to set a temperature of about 35/40 ° C on the
handwheel with the graduated scale (for a detailed description of the
thermostatic control regulation refer to the sheet instructions in its
package).
The three-way mixing valve, on the other hand, is equipped with a
manual regulation bypass which allow to regulate the circulation of the
heat-carrying fluid coming from the heat generator in the event that
the mixing valve is completely closed and does not allow anything to
pass toward the collector of the low-temperature circuit of the radiant
panel.
TECHNICAL DATA:
Working fluid: Water and glycol solutions
Maximum percentage of glycol: 30%
Primary input temperature range: 5÷110°C
Temperature adjustment range: 20÷50°C
Maximum operating pressure: 10 bar
Minimum operating pressure: 0,8 bar
MATERIALS:
Valve body and fittings: Brass CW617N – UNI EN 12165
Caps and unions: Brass CW617N – UNI EN 12165
Sealing elements EPDM Perox
1″