Male/female two-way full bore zone ball valve, with servomotor with relay and auxiliary microswitch for potential-free contact
Max. working pressure 16 bars
Max. differential pressure 10 bars
Max. working temperature 110°C.
Function
The zone valves are aimed at automatically controlling and diverting the fluids in
heating, air conditioning and sanitary water systems.
They are controlled by a servo-control, connected to a room thermostat provided with
automatic return function, regulating the ambient temperature. All servomotors are
equipped with an auxiliary micro-switch to control the pump.
This product, easy to install, shows high hydraulic performance in reduced sizes, this
makes it specially suitable for zone heating installations.
Advantages of the zone ball valves:
– Excellent seal
– Quick opening/closing time
– Low pressure drop rates
– Operation under high differential pressures
Advantages of the ICMA zone valves:
– Soft seat ball movement, valve opening torque < 45 lbf-in 6 Nm
– Quick connection system
– The motor can be used manually as a release device in the event of power failure
– Highly reliable motor, manufactured in Switzerland
– High precision gears, in sintered metal materials
– Low noise level .
– Motor start-up torque doubled if compared with the valve body
– Quick and repeatable motor lock/unlock, without damaging the motor or the valve
– Severe and rigorous factory testing and quality control procedure (50.000 cycles)
VALVE BODY
Body: Brass CW617N UNI 12165
Control stem: Brass CW617N UNI 12164
Ball: Brass CW617N UNI 12164 Chromium plated
Ball sealing gasket: PTFE
O-Ring: EPDM PEROX – (high resistance)
SERVOCONTROL
Upper protection shell: Clear ABS
Lower protection shell: Nylon 66 Nero
PERFORMANCES
VALVE BODY
Working fluids: water, glycol-based solutions Max 50%
Max. operating ‘pressure: 10 bar
Temperature range: 23°/230°F (-5°/110°C)
Max. differential pressure: 10 bar
SERVOCONTROL
Synchronous motor: 230 VAC (±10%) 50÷60 Hz
Power absorbed: 5VA
Max. ambient temperature: 55°C
Capacity of the auxiliary micro-switch contacts: Max 1A
Protection degree: IP 44 vertical control stem – IP 40 (casing)
Movement time (90° rotation angle): 45 sec.
Dynamic start up torque: 12 Nm
Cable length: 1 m
Standard operating mode: NC (normally closed)
Size | Voltage | Code |
1/2″ | 230 volt | 82341AD0553 |
3/4″ | 230 volt | 82341AE0553 |
1″ | 230 volt | 82341AF0553 |
1″1/4 | 230 volt | 82341AG0553 |