The Hydro EN pump set is designed in compliance to EN 12845 standard for operation with clean fresh water in automatic sprinkler systems, hydrant networks and compartments for installation of firefighting pump sets.
General information:
Product name: Hydro EN 40-250/250 S2JS
ADL-U1
Product No: 99843949
EAN number: 5713835083975
Technical:
Rated flow: 64.1 m³/h
Rated head: 72.9 m
Electric cooling flow: 1 m³/h
Nominal impeller diameter: 250 mm
Approvals: CE
Fire standard: EN 12845
Number of pumps: 3
Backup pumps: 1
Main pump type: NKF 40-250/250
Number of electrical driven pumps: 2
Jockey pump type: CM3-13
Number of Jockey pumps: 1
Materials:
Pump housing: Cast iron
Pump housing: EN-GJL-250
Impeller: Bronze
Manifold: Galvanized steel
Installation:
Range of ambient temperature: 5 .. 40 °C
Relative humidity: 50 %
Maximum operating pressure: 16 bar
Type of inlet connection: DIN
Type of outlet connection: DIN
Size of inlet connection: DN 65
Size of outlet connection: DN 65
Type of inlet connection for Jockey
pump:
Rp
Size of inlet connection for Jockey
pump:
1 1/4 inch
Earth connection: PE
Elevation above sea level: 1000 m
Liquid:
Pumped liquid: Water
Liquid temperature range: 0 .. 40 °C
Selected liquid temperature: 20 °C
Density: 998.2 kg/m³
Electrical data:
Motor standard: IEC
Driver type: Electric Motor
Mains supply for electrical motor: 3 x 400 V
Rated power – P2: 22 kW
Mains frequency: 50 Hz
Rated current: 38.5 A
Starting current: 750 %
Motor nominal speed (w/o slip): 2980 rpm
Number of poles: 2
Method of start: Direct-on-line (DOL)
Enclosure class (IEC 34-5): IP54
Motor standard for Jockey pump: IEC
Mains supply for jockey motor: 3 x 400 V
Rated power – P2 for Jockey pump: 2.2 kW
Rated current for Jockey pump: 4.6 A
Number of poles for Jockey pump: 2
Method of start for Jockey pump: Direct-on-line (DOL)
Others:
Net weight: 883 kg
Gross weight: 1020 kg